Four years, six months, a 2 percent error rate: what the guideline values in DGUV Vorschrift 3 mean and how to set inspection intervals in your risk assessment.

§ 5 of DGUV Vorschrift 3 requires electrical installations and equipment to be inspected before being put into service for the first time, after modification or repair, and thereafter at specified intervals. The intervals must be set so that defects that can be expected are detected in good time. The regulation itself does not specify a fixed figure. The well-known values come from the implementing instructions (Durchführungsanweisungen) and are guideline values for normal conditions.

The guideline values

For fixed installations and equipment, the implementing instructions specify four years, and one year for workplaces, rooms and installations of a special kind, in each case by an electrically skilled person. Users trip residual current devices in stationary installations every six months using the test button, and every working day in non-stationary installations such as construction sites.

For portable equipment, extension cables and appliance connection cables, the guideline value is six months, and three months on construction sites. If the error rate is below 2 percent, the interval can be extended. As maximum values, the implementing instructions give one year for construction sites, production facilities and workshops, and two years for offices and similar areas.

The error rate is the proportion of inspections with defects in a comparable area, such as the workshop or administration. DGUV Information 203-071 points out that devices that are already rejected at the visual inspection and disposed of straight away must be included in the count. Otherwise, the rate looks better than it is.

The interval belongs in the risk assessment

Under § 3 Abs. 6 of the Industrial Safety Regulation (Betriebssicherheitsverordnung), the employer determines and sets the type, scope and intervals of the necessary inspections as part of the risk assessment. DGUV Information 203-071 requires deviations from the guideline values to be justified. The employer remains responsible for ensuring that the intervals are plausible.

The assessment takes into account stress and environment, frequency of use, the qualifications of the users and the results of previous inspections. A hammer drill on a construction site and a kettle in the staff kitchen are both portable, yet they need very different intervals.

Inspections may be carried out by an electrically skilled person. For portable equipment, an electrically instructed person may also carry out inspections if they use suitable measuring and testing equipment. For inspections under § 14 of the Industrial Safety Regulation, the person must also be appointed as a person qualified to carry out inspections. TRBS 1203 describes the requirements.

Revision announced

On 17 July 2026, the DGUV announced that it is revising Vorschriften 3 and 4. The inspection requirement is to become more practical and risk-based, while the level of protection is to be maintained. A text of the new version is not yet publicly available, and the existing regulation applies until then. The DGUV emphasises that businesses can already set their own inspection intervals today based on the risk assessment and the error rate, and that longer intervals are justifiable for equipment subject to little stress.